Продукт
Yokogawa | A2LP131-S00 PROFINET Communication Module
A2LP131-S00
The Yokogawa A2LP131-S00 is a specialized PROFINET IO-Controller communication module designed for CENTUM VP integrated production control systems. Operating as a master controller, it exchanges process data and alarm notifications with PROFINET IO-Devices at 100 Mbps via an IEEE 802.3 100BASE-TX RJ-45 port.
Seamless Integration of Industrial Ethernet with DCS Architectures
In continuous process and hybrid automation industries, connecting modern field smart instruments and subsystem controllers to a central Distributed Control System (DCS) requires fast, standardized communication protocols. The Yokogawa A2LP131-S00 PROFINET Communication Module acts as an advanced PROFINET IO-Controller within the Yokogawa CENTUM VP platform. Installed directly into Field Control Stations (FCS) or expansion ESB node units, the module establishes high-speed 100 Mbps data exchange with field PROFINET IO-Devices, bringing field-level diagnostic and measurement data into central control function blocks.
Certified Compliance and Robust System Capabilities
The A2LP131-S00 module is officially certified to comply with PROFINET Specification Version 2.35 Conformance Class A (CC-A), while also supporting CC-B and CC-C devices within the CC-A functional scope. Each module features a single IEEE 802.3 100BASE-TX physical interface using a standard RJ-45 connector and 2×2 twisted-pair shielded cabling over segment distances up to 100 meters.
With an I/O communication data capacity of 1000 words per module and support for up to 128 connectable PROFINET IO-Devices, the A2LP131-S00 allows control engineers to map data types—including Boolean, Integer16/32, Unsigned16/32, and Float32—directly into CENTUM VP regulatory and sequence control function blocks.
Alarm Handling, Network Redundancy, and Modular Design
Beyond standard cyclic data transmission, the A2LP131-S00 actively processes alarm messages generated by field IO-Devices and routes notifications instantly to the Field Control Unit (FCU). In high-availability architectures, the module supports PROFINET network communication path dual redundancy when configured with managed switches running Media Redundancy Protocol (MRP) in a ring topology.
Compact and lightweight at approximately 0.31 kg, the module measures 32.8 mm in width, 125.5 mm in depth, and 130 mm in height. It operates on a maximum current consumption of 0.8 A, maintaining low thermal output in control cabinets.
Applications
-
Distributed Control Systems (DCS): Integration of field-level PROFINET IO-Devices into Yokogawa CENTUM VP control station architectures.
-
Oil & Gas Processing: High-speed Ethernet interfacing with motor management systems, flow skids, and smart instrumentation.
-
Chemical & Petrochemical Operations: Real-time data exchange between central control units and packaged reactor or dosing skids.
-
Power Generation Facilities: Field bus communication with turbine control auxiliaries and electrical protection relays.
-
Water & Wastewater Utilities: Centralized monitoring of remote pumping stations and analytical equipment over industrial Ethernet.
Technical Specifications
-
Manufacturer: Yokogawa
-
Product Model: A2LP131-S00
-
Product Type: PROFINET Communication Module (for N-IO/FIO)
-
Role: PROFINET IO-Controller
-
PROFINET Certification: Version 2.35 Conformance Class A (CC-A)
-
Physical Layer Interface: IEEE 802.3 100BASE-TX
-
Connector Type: RJ-45 (1 physical port)
-
Transmission Speed: 100 Mbps
-
Transmission Cable & Distance: 2×2 twisted-pair shielded cable, max. 100 m per segment
-
Max. Connectable Devices: Up to 128 PROFINET IO-Devices per module
-
I/O Data Capacity: 1000 words per module
-
Maximum Current Consumption: 0.8 A
-
Module Weight: Approx. 0.31 kg
-
Dimensions (W x D x H): 32.8 mm x 125.5 mm x 130 mm
-
Compatible FCS Models: AFV30S, AFV30D, AFV40S, AFV40D, A2FV50S, A2FV50D, A2FV70S, A2FV70D
-
Compatible Node Units: ANB10D, ANB10S, ANB11D, ANB11S
FAQ
Q1: What is the primary function of the Yokogawa A2LP131-S00 module? A: The A2LP131-S00 acts as a PROFINET IO-Controller master module in Yokogawa CENTUM VP systems, exchanging process data and alarms with field PROFINET IO-Devices.
Q2: What is the exact module weight and dimensions of the A2LP131-S00? A: According to Yokogawa specification sheet GS 33J60G90-01EN, the module weighs approximately 0.31 kg and measures 32.8 mm (W) x 125.5 mm (D) x 130 mm (H).
Q3: How many PROFINET IO-Devices can a single A2LP131-S00 module support? A: A single A2LP131-S00 module supports up to 128 connectable PROFINET IO-Devices with a maximum communication I/O data capacity of 1000 words.
Q4: Which CENTUM VP software revisions support the A2LP131 module? A: The module requires CENTUM VP R6.07 or later, using control functions VP6F1700, VP6F1800, or VP6F1900 along with engineering tool VP6E5100.
Документы продукта
Открыть технические документы.
Один раз укажите рабочую почту и WhatsApp для доступа ко всем документам.