Produit
Yokogawa SDV541-S53/B4S00 Digital Output Module ProSafe-RS 16-Channel 24V DC
SDV541-S53/B4S00
The Yokogawa SDV541-S53/B4S00 is a 16-channel 24 V DC digital output module designed for ProSafe-RS safety Instrumented systems to control field equipment such as valves and relays. It features built-in field wiring diagnostic functions and module isolation, ensuring high reliability and dual-redundant operational stability in harsh industrial environments.
The Yokogawa SDV541-S53/B4S00 is a high-performance 16-channel digital output module specifically engineered for deployment in Yokogawa ProSafe-RS Safety Instrumented Systems (SIS). Serving as a critical interface between safety logic solvers and final control elements, this digital output module transmits precise 24 V DC ON/OFF status signals to control solenoids, relays, alarms, and emergency shutdown devices across demanding process automation environments.
Model Breakdown & Configuration Details:
-
Model Code (SDV541): Digital Output Module with 16 channels and module isolation.
-
Suffix Code (-S): Standard type execution.
-
Suffix Code (5): Designed for pressure clamp terminal block or MIL cable connections with standard non-explosion protection.
-
Suffix Code (3): Features ISA Standard G3 conformal coating and an extended operating temperature rating of -20 °C to 70 °C.
-
Option Code (/B4S00): Equipped with a dedicated pressure clamp terminal block for digital output (Model: STB4S-00, without surge absorber).
Advanced Diagnostics & Dual-Redundant Support: A key capability of the SDV541 module is its built-in field wiring diagnostic functionality. The unit actively monitors the integrity of external wiring loops for open circuits and short circuits in real time, eliminating the need for external wiring diagnosis elements or auxiliary resistors. Furthermore, the SDV541 supports dual-redundant configurations, allowing seamless unit-level redundancy to prevent unnecessary process trips and ensure uninterrupted safe plant operation.
Robust Design for Harsh Industrial Conditions: Designed to withstand aggressive industrial settings, the SDV541-S53/B4S00 complies with ISA Standard G3 harsh environment standards, offering superior resistance to corrosive airborne contaminants. Its current source output design delivers up to 0.2 A per channel (3.2 A total per module), ensuring reliable operation for solenoid valves and control actuators under high load conditions.
Applications
-
Emergency Shutdown Systems (ESD): Reliable tripping of field safety valves and shutdown actuators.
-
Fire and Gas Systems (F&G): Actuation of visual/audible alarms and fire suppression release valves.
-
Burner Management Systems (BMS): Safe fuel gas shut-off control in industrial boilers and furnaces.
-
Oil & Gas Processing: Onshore and offshore safety instrumented loop execution.
-
Chemical & Petrochemical Plants: Control of critical process interlocks and safety valves.
-
Power Generation Facilities: Automated protection loops for steam turbines and auxiliary machinery.
Technical Specifications
| Item | Specification Details |
| Model | SDV541 |
| Suffix Code | -S53 |
| Option Code | /B4S00 (Includes STB4S-00 pressure clamp terminal block without surge absorber) |
| Number of Outputs | 16-channel, module isolation |
| Output Voltage | 24 V DC |
| Output Voltage Drop | 1 V maximum |
| External Power Supply Rating | 24 V DC (+20% / -10%), 3.4 A minimum |
| Output Format | Current source |
| Maximum Load Current | 0.2 A / output line (3.2 A in total output lines) |
| Minimum Load Current | 35 mA |
| Load Resistance Range | 120 to 685 Ω |
| Max Leak Current at OFF Status | 1.6 mA |
| Output Response Time | 30 ms maximum |
| Withstand Voltage | 2 kV AC between output signal lines and system for 1 minute |
| Current Consumption | 300 mA max (5 V DC), 150 mA max (24 V DC) |
| Environmental Standard | ISA Standard G3 Compliant |
| Operating Temperature | -20 °C to 70 °C |
| Dimensions (W × H × D) | 32.8 mm × 130 mm × 107.5 mm |
| Weight | Approx. 0.29 kg (module with terminal block) |

FAQ
Q1: What does the option code /B4S00 include for the SDV541 module?A: Option code /B4S00 includes a dedicated pressure clamp terminal block for digital output without an integrated surge absorber (Terminal block model: STB4S-00).
Q2: Does the SDV541 module require external resistors for field wiring diagnostics?A: No, the SDV541 incorporates internal field wiring diagnostic functions that automatically detect open circuit or loop faults without requiring external wiring diagnosis elements.
Q3: Can the Yokogawa SDV541 digital output module be configured for dual redundancy?A: Yes, SDV541 modules can be configured as dual-redundant pairs in the ProSafe-RS safety system to enhance overall system availability and prevent false trips.
Q4: What is the operating temperature range for the -S53 version?A: Suffix code 3 indicates that the module is certified for an extended operating temperature range of -20 °C to 70 °C and includes ISA Standard G3 conformal coating protection.
Documents produit
Déverrouiller les documents techniques.
Saisissez une fois votre e-mail professionnel et WhatsApp pour accéder aux documents.