01Temperature MeasurementTemperature measurement uses temperature sensors, thermocouples, RTDs and other instruments to accurately detect and monitor process temperatures. 02Level MeasurementLevel measurement uses ultrasonic level meters, radar level meters, and other instruments to detect and monitor the level or height of materials in tanks, vessels, and process equipment. 03Pressure MeasurementPressure measurement uses pressure transmitters, differential pressure transmitters, and other instruments to detect and monitor pressure and pressure changes in pipelines, tanks, and process equipment. 04Flow measurementFlow measurement uses electromagnetic, ultrasonic, vortex, and mass flow meters to detect and monitor the flow of liquids, gases, or steam in pipelines. 05DCSYokogawa DCS cards are core modules of a distributed control system, used to acquire field signals such as temperature, pressure, and flow, while providing control, output, and communication functions. 06Water Quality AnalysisWater quality analysis uses water quality analyzers and online monitoring instruments to detect and monitor key parameters such as pH, dissolved oxygen, turbidity, conductivity, and residual chlorine in water. MODELE+H Proline Promass I 100 Coriolis FlowmeterDesigned for accurate multi-variable measurement of liquids and gases, this Coriolis flowmeter delivers simultaneous in-line viscosity, density, and mass flow data with minimal pressure loss. It features an ultra-compact transmitter and a robust single-tube titanium measuring system for demanding industrial processes. MODELYOKOGAWA A2EE3A-TN | ESB Bus Adapter Connector UnitThe YOKOGAWA A2EE3A-TN ESB Bus Adapter is engineered for Yokogawa CENTUM VP system architecture to connect and terminate the ESB bus at ANT522 optical repeater slave modules. Built for secure terminal connection and signal stability, this component ensures seamless communication extension across industrial automation networks. MODELE+H Levelflex FMP56 Guided Wave Radar Level TransmitterDesigned for continuous level measurement of powdery to granular bulk solids in tall silos and storage vessels, this cost-effective guided wave radar transmitter remains unaffected by heavy dust, filling noise, or thermal stratification. Featuring a high-tensile rope probe capable of withstanding pulling forces up to 12 kN, it integrates HistoROM data management and optional Bluetooth functionality for safe and efficient operation. MODELE+H Proline Promass X 300 Coriolis Mass FlowmeterThe Endress+Hauser Proline Promass X 300 is a maximum-capacity Coriolis mass flowmeter engineered for high-volume measurement of crude oil, refined hydrocarbons, chemicals, and industrial gases up to 4,100 t/h. Featuring a patented four-tube sensor system and integrated Heartbeat Technology, it offers exceptional operational efficiency, minimal pressure drop, and custody-transfer precision for large-scale energy and industrial processing applications. MODELChongqing Chuanyi MS22PSB2D10B0060DMZ Magnetostrictive Level GaugeEngineered for ultimate reliability and high-accuracy fluid monitoring, the MS Series Magnetostrictive Liquid Level Transmitter delivers continuous, real-time measurements for total liquid level and interface positions in demanding industrial environments. Utilizing advanced magnetostrictive sensing technology, this versatile transmitter provides precise, non-contact signal processing with a measurement accuracy up to ±1mm, making it an ideal solution for critical process controls across chemical processing, oil and gas, power generation, and water treatment applications where long-term stability and explosion-proof durability are paramount. MODELE+H FMU30 Non-Contact Ultrasonic Level TransmitterThe Prosonic FMU30 Non-Contact Ultrasonic Level Transmitter provides highly accurate, maintenance-free continuous level and open-channel flow measurement for liquids, pastes, and coarse bulk solids across municipal and industrial applications. Featuring an integrated temperature sensor for automatic sound velocity compensation, a user-friendly 4-line plain text display with 32-point linearization, and a rugged IP68-rated weatherproof enclosure, this compact 2-wire transmitter delivers dependable real-time tank monitoring, pump control, and overflow protection in sewage treatment plants, process water storage, and chemical buffer tanks. MODELE+H Deltabar PMD55B High Precision Smart Differential Pressure TransmitterThe PMD55B High Precision Smart Differential Pressure Transmitter delivers exceptionally accurate differential pressure, flow, and hydrostatic level measurements for industrial liquids, gases, and steam. Featuring a robust metallic diaphragm, ultra-low long-term drift, optional wireless Bluetooth operation, and SIL2/3 functional safety certifications, this versatile instrument provides stable, error-free process monitoring across harsh chemical, oil, and water treatment environments. MODELE+H Waterpilot FMX11 Submersible Hydrostatic Level TransmitterThe Waterpilot FMX11 is a high-precision, heavy-duty submersible hydrostatic level transmitter engineered for continuous liquid level and depth monitoring in fresh water, groundwater wells, drinking water reservoirs, and surface water bodies. Featuring an ultra-compact 22mm stainless steel 316L housing, an integrated atmospheric pressure compensation tube with a protective Teflon filter, and international drinking water certifications, this compact dip cell sensor delivers exceptional long-term stability and precise 4–20 mA signal output even in narrow 1-inch pipes and demanding environmental conditions. MODELChongqing Chuanyi WZGPK-73DH-GB/1P2-AJ150G-M20XC6-AXX-I5/2AM20 Explosion-proof RTDThe WZGPK is a heavy-duty explosion-proof armored Pt100 RTD temperature sensor engineered for accurate thermal monitoring in hazardous industrial environments. Equipped with a high-precision Class A platinum sensing element, a 3-wire connection, a 6mm diameter sheath made of durable 321 stainless steel, and a 150mm insertion length, this flameproof sensor delivers exceptionally fast thermal response, vibration resistance, and long-term stability across a wide temperature range from -200°C to 600°C. Designed with an M20x1.5 process thread and an explosion-proof junction box, it provides reliable flameproof protection and continuous signal accuracy for chemical plants, oil refineries, and automated process control systems. MODELYokogawa ADV151-P50/D5A00 Digital Input Module ExstockEngineered for reliable industrial automation, the Yokogawa ADV151-P50/D5A00 Digital Input Module provides high-density 32-channel, 24 V DC isolated signal processing alongside dedicated connection adapters, ensuring optimal signal integrity, robust noise immunity, and seamless integration into distributed control systems (DCS). MODELYokogawa AAI143-H50 Analog Input Module ExstockThe Yokogawa AAI143-H50 is a high-performance 16-channel isolated analog input module designed for process automation systems, capable of handling 4 to 20 mA standard signal inputs with exceptional stability and accuracy. Supplied with its matching terminal block adapter, this module offers seamless integration, superior noise immunity, and reliable data acquisition for demanding industrial environments. MODELYokogawa S2CP471-01 Controller Module Spare Part ExstockThe Yokogawa S2CP471-01 Controller Module Spare Part provides reliable, real-time control performance and high-speed VNET/IP communication connectivity to optimize your industrial DCS automation system with seamless integration and reduced operational downtime. SOLUTIONSmart water network monitoringCombine verified flow and pressure data for distribution monitoring and operational review. SOLUTIONHydrogen pressure measurementReview materials, pressure range and safety requirements for hydrogen process measurement. SOLUTIONProcess measurement selectionStart from the medium, operating window, installation and required signal before selecting an instrument.

Yokogawa AAI143-H50/A4S10 Analog Input Module

AAI143-H50/A4S10 Analog Input Module

The Yokogawa AAI143-H50/A4S10 is a high-density 16-channel isolated analog input module designed to acquire standard 4 to 20 mA DC process signals from field transmitters into DCS control systems. Featuring 1500V AC signal isolation, channel-by-channel 2-wire/4-wire configuration, and dual-redundancy support, it provides reliable, noise-immune data acquisition for critical industrial process automation.

Yokogawa AAI143-H50/A4S10 16-Channel Analog Input Module with Terminal Block

Reliable Process Signal Acquisition with Yokogawa AAI143-H50/A4S10

The Yokogawa AAI143-H50/A4S10 Analog Input Module is an industrial-grade, 16-channel isolated current input module built for high-density signal integration in distributed control systems (DCS). Operating on standard 4 to 20 mA DC current loops, this module converts real-time field measurements—such as pressure, flow, temperature, and level—into precise digital data for process visualization, monitoring, and control loops. Equipped with the /A4S10 option (Model ATA4S-10 pressure clamp terminal block with built-in surge protection), the unit simplifies field wiring while protecting system electronics against outdoor voltage transients and electrical noise.

High-Density Isolation and Dual-Redundancy Protection

Process plants require continuous operation without downtime caused by field wiring faults or unexpected voltage spikes. The AAI143-H50 module delivers robust galvanic channel-to-system isolation withstand voltages up to 1500V AC for one minute. This electrical barrier prevents ground loops, reduces signal interference, and guards sensitive central control units from field surges. For mission-critical control loops, the AAI143-H50/A4S10 fully supports dual-redundant deployment. When installed in pairs, the module ensures automatic failover, maintaining uninterrupted data collection even during hardware maintenance or channel faults.

Flexible Transmitter Compatibility and Smart Features

Designed for seamless field integration, each channel on the AAI143-H50/A4S10 can be individually configured via hardware jumpers to interface with either 2-wire or 4-wire transmitters. The module supplies stable loop power (19.0 to 25.5 V DC) to 2-wire instruments, eliminating the need for external power supplies. Additionally, the module delivers rapid signal updates with a 10 ms data refresh rate, enabling fast control responses in dynamic industrial processes. Its durable circuitry withstands wide ambient operating temperatures, making it suitable for standard control rooms and remote equipment enclosures alike.

Applications

  • Oil & Gas Processing: High-density current signal acquisition for wellhead control systems, pipeline monitoring, and tank farm automation.

  • Chemical & Petrochemical Plants: Precision monitoring of continuous chemical reactors, distillation columns, and safety interlocks.

  • Power Generation: Accurate data collection from boiler feedwater transmitters, steam temperature sensors, and turbine control loops.

  • Water & Wastewater Treatment: Multi-channel flow, pressure, and analytical sensor integration across municipal and industrial treatment facilities.

  • Pharmaceutical Manufacturing: Reliable 4-20 mA data acquisition ensuring strict process compliance and batch control integrity.

Technical Specifications

Parameter Specification Details
Model Number AAI143-H50/A4S10
Product Type Analog Input Module (4 to 20 mA DC)
Number of Channels 16 channels, isolated
Input Signal Range 4 to 20 mA DC
Allowable Input Current 24 mA max
Withstanding Voltage 1500 V AC for 1 minute (Input to system)
Input Resistance Power ON: 270 Ω (20 mA) to 350 Ω (4 mA); Power OFF: ≥500 kΩ
Measurement Accuracy ±16 µA
Data Update Period 10 ms
Transmitter Power Supply 19.0 V DC or higher (at 20 mA), current limited to 25 mA
Transmitter Compatibility 2-wire or 4-wire (set per channel by jumper pin)
Temperature Drift ±16 µA / 10°C
Redundancy Supports dual-redundant configuration
Power Consumption 230 mA (5 V DC), 540 mA (24 V DC)
Terminal Block Option /A4S10 (Pressure Clamp Terminal Block ATA4S-10 with surge absorber)
Weight Approx. 0.3 kg

AAI143-H50/A4S10 Analog Input ModuleFAQ

Q1: Can the Yokogawa AAI143-H50/A4S10 be used in a dual-redundant system?

A: Yes, the AAI143-H50 module fully supports dual-redundant configurations, allowing two modules to operate in parallel to prevent system downtime.

Q2: Does this module supply power to field transmitters?

A: Yes, it includes built-in loop power supply capability (19.0 V DC or higher at 20 mA) for 2-wire transmitters. It can also be configured for self-powered 4-wire transmitters channel-by-channel using internal setting pins.

Q3: What terminal block is included with the /A4S10 suffix option?

A: The /A4S10 option designates the ATA4S-10 pressure clamp terminal block, which features built-in surge absorbers to protect signal lines against transient overvoltages.

Q4: Is channel-to-system isolation provided on the AAI143-H50?

A: Yes, it features 1500V AC isolation between the input channels and the system logic, protecting the control system against external electrical noise and ground voltage differences.