Produkt
JUMO CANtrans T RTD Temperature Probe with CANopen Output
CANtrans T
Designed for reliable temperature measurement in liquid and gas media, the JUMO CANtrans T RTD temperature probe features a robust vibration-resistant construction with a digital CANopen output interface. It is widely applied across medical technology, mechanical engineering, drive technology, commercial vehicles, and railway systems.
High-Precision Digital Signal Processing
The internal measuring insert utilizes a Pt1000 sensor in a two-wire circuit, providing a sampling rate of 250 ms. The digital processing architecture allows measured values to be directly output in degrees Celsius, Fahrenheit, or Kelvin, with user-selectable decimal places (0, 1, or 2).
Comprehensive Device Functions (CiA Profile DS 404)
Adhering to the CiA DS 404 profile, the probe offers extensive auxiliary and monitoring functions accessible via standard CANopen software tools and EDS object directories:
-
Sensor Monitoring: Continuously checks sensor integrity and triggers high-priority emergency telegrams in case of a probe break or short circuit.
-
Filter & Scaling: Adjustable filter constants suppress undesired signal fluctuations, while scaling functions adapt the output to custom measuring units.
-
Min/Max Indicator: Integrated drag indicator functions save minimum and maximum measured temperature peaks.
-
Fine Adjustment: Features a freely adjustable characteristic line offset.
Rugged Mechanical & Electrical Build
The unit is housed in a vibration-resistant stainless steel (1.4571) protection tube and process connection, ensuring a reliable seal against underpressure and overpressure. Electrical connection is established via a reliable 5-pole M12x1 round plug (IEC 60947-5-2), yielding an IP67 protection rating when screwed on.
Applications
The JUMO CANtrans T temperature probe is ideal for continuous temperature monitoring in diverse industrial sectors:
-
Mechanical Engineering & Drive Technology: Gearboxes, compressors, and hydraulic power units.
-
Commercial Vehicles & Railway Systems: Engine monitoring, cooling systems, and mobile machinery.
-
Medical Technology & Process Automation: Skid-mounted units, fluid distribution systems, and general industrial plant engineering.
Technical Specifications
-
Basic Types: 902910/10 (Standard), 902910/12 (Extension tube version for higher temperatures)
-
Measuring Range: -50 to +150 °C (Code 370) or -50 to +450 °C (Code 404)
-
Measuring Insert: 1 x Pt1000 or 2 x Pt1000 (DIN EN 60751, Class B, two-wire circuit)
-
Output Signal: CANopen according to CiA DS 404 V1.2
-
Communication Profile: CiA DS 301 V4.02 (CAN Slave), Baud rate 20 kBaud to 1 MBaud
-
Voltage Supply: DC 10 to 30 V (Current consumption max. approx. 45 mA)
-
Process Connection: Screw connection (G 1/4, G 3/8, G 1/2, M14×1.5, M18×1.5, M20×1.5, 1/2-14 NPT)
-
Protection Tube Material: Stainless steel 1.4571 (Diameter Ø 6 mm)
-
Electrical Connection: Round plug M12×1, 5-pole (IEC 60947-5-2)
-
Protection Type: IP67 according to EN 60529 (with connected plug)
-
Response Time: t0.9 = 12 s in water 0.2 m/s
FAQ
Q1: How do I configure the parameters and baud rate of the CANtrans T?
A: All device parameters, module IDs (1 to 127), and baud rates can be easily set using standard CANopen software tools via LSS, SDO, or the device object directory (EDS file).
Q2: What is the difference between basic type 902910/10 and 902910/12?
A: Basic type 902910/10 is the standard RTD temperature probe design, whereas 902910/12 includes an extension tube specifically engineered to handle higher operating temperatures up to +450 °C safely.
Q3: Does the probe provide error detection if the sensor fails?
A: Yes. The built-in sensor monitoring continuously checks sensor functionality and automatically triggers high-frequency emergency telegrams and status flags in the event of a probe break or short circuit.